Handling the heat of transformers
02Oct
posted by: Tony Harper, Eastern Transformers & Equipment (ETE)

Figure 1 – Classification of Insulating Materials – maximum operating temperatures
Transformers generate heat. This is a completely normal phenomenon and is something that will occur regardless of the size or rating of the transformer.
(Click here to view article in digital edition)
A transformer feeling warm, or even hot, to touch is rarely an issue and is, in fact, typical of a working transformer. It is the extent to which a transformer’s temperature rises above the ambient temperature that should be considered when measuring whether it is running too hot.
Transformers are designed to different insulation classes, depending on their proposed application. This insulation class will determine the temperature range to which the transformer can efficiently run. As such, different transformers will be capable of working within different temperature boundaries. Accordingly, there is no universal temperature figure that can be used to measure whether a transformer is running excessively hot.
The ‘Classification of Insulating Materials’ outlines the maximum operating temperature for each insulation class however, which, when used alongside the commonly accepted maximum ambient temperature of 40°C, can determine the maximum temperature rise of a transformer (maximum operating temperature – maximum ambient temperature). Transformers utilising Class Y insulation materials can run up to a maximum of 90°C, whereas those designed with Class C insulation materials can run in excess of 180°C, without damaging the insulation or affecting the transformer’s life. This illustrates the vast difference in what can be considered normal when measuring the running temperature of a transformer and exemplifies why a transformer feeling hot to the touch is not, necessarily, an indication of the transformer overheating.
Temperature reduction mechanisms
Ambient temperature build-up can be defined as the average temperature rise of the windings above the ambient (surrounding) temperature when the transformer is loaded to its full specified rating. Temperature is one of the biggest contributing factors to the life of transformers, with increased temperature acting as a fundamental cause for reduced transformer life. As such, ambient temperature build-in is an occurrence that, if not considered during the specification process, can lead to transformers running too hot and, subsequently, failing.

Figure 2 – A custom-built transformer from ETE with ducting of the windings, allowing air to flow over the windings to cool the transformer
The heat a transformer produces when running rises and causes the temperature within the enclosure, of which the transformer is housed, to increase. The internal ambient temperature (within the enclosure) will be a lot higher than that external to the enclosure. Temperature readings should, therefore, be taken based on the temperature of the transformer itself to give an accurate indication of the actual ambient temperature.
If the temperature reaches a point where it is deemed too high, temperature reduction mechanisms will be required (e.g. cooling fans) to ensure the continued smooth running of the transformer. These fans are used to either extract the excess heat or blow air into the enclosure. The extraction of excess hot air is, generally, the preferred method as this allows for additional air to enter via an open vent or inlet filter. The overall running temperature of the transformer is calculated, not only by the amount of heat generated, but by the amount of heat removed. Thermostats control when fans turn on and off, using pre-set temperature parameters, to ensure an optimum temperature is maintained within the enclosure (and that the fans are not continuously blowing).
Eastern Transformers & Equipment (ETE) have compiled an extensive array of stock products that make up their thermal management range. The products within this collection have all been added to ensure that transformers can effectively work within an optimum environment for their designed application. Most of the products (e.g. fans, filters, and thermostats) have been designed to ensure the internal temperature of the enclosure remains within the specified boundaries. Anti-condensation heaters are also available to reduce the risk of moisture affecting the insulating qualities of the transformer (another concern that can affect the life of a transformer).
Air cooling
The bigger the size of a transformer the more difficult it is to cool. Consequently, air cooling of windings becomes more and more critical as transformers get bigger. This can be achieved by ducting of the windings; a method that allows air to flow over the windings. This is a vital element in ensuring larger transformers continue to run at a temperature within the specified guidelines and is an important part of the inherent transformer design.

Figure 3 – ETE’s stock thermal management range helps to ensure transformers are operating within an optimum environment
Where ducting of the windings is present, air can be forced through the ducts which can lead to a temperature reduction of up to 50%. For example, a transformer previously running at 120°C could run as low as 60°C by utilising this method. The efficiency of this process will, ultimately, depend on the power of the fans used.
Modern innovations
Fans are mechanical devices and are, therefore, susceptible to failure over time. Microprocessor temperature control units are a modern technology that aim to reduce the likelihood of fan burn-out by controlling when they switch on and off. What’s the difference between a temperature control unit and a standard thermostat? Thermostats control the temperature within an enclosure, whereas temperature control units monitor the specific temperature within the transformer windings. The units can be linked into PTC probes for more efficient control of the cooling fans. The fans will only cut in, when necessary, to bring the windings back into range. Fans are not designed for continuous use and using microprocessor temperature control units, instead of thermostats, will ensure that their life span is preserved for much longer. Additionally, the control units can switch off the transformer in the event of over temperature.
About the author:
Tony Harper is Marketing Manager for ETE and is now in his third year with the company. Tony achieved a First Class degree in BSc Psychology from Coventry University and has been utilising the psychological principles developed, along with his creative flair, to manage all aspects marketing within his current position. Whether it be brochure design, website maintenance, or telemarketing his across-the-board prowess is continuously growing.